About foam fire-extinguishers
View  foam fire-extinguishers catalog


Method of use

  1. Foam extinguishing devices are designed for extinguishing of hard substances of organic origin (wood, paper, fabric etc.) and various kinds of explosive and dangerous fluids (petrol, oils, grease, spirits, etc.) with a foam solution on the initial stage of inflammation.
    Fire class definition – A and B.
    Devices can be used also for extinguishing gas fire (C class).
  2. Devices are operable in the regions with a moderate climate with temperature of environment from +1C to +60C disposing them both inside and outside ensuring their protection from heat and atmospheric precipitation.
  3. Device can be placed on wall with a help of suspension parts available in the kit and within a hand’s reach. Devices can be placed on the floor, special cabinets, niches, etc.
  4. Recommended places for disposal of foam extinguishers: various public premises, academies, offices, banks, shops, hospitals, hotels, restaurants, theatres and cinema theatres, passenger railway cars, specific working places related to flammable liquids, etc.

Construction and principles of operation

  1. Device consists of a pressure-proof metal shell (covered with plastic from inside) filled with a fire extinguishing substance – water + AFFF kind of foam concentrate and a launch mechanism and a rubber hose with a foam creating muzzle attached.
  2. Shell must be under permanent nitrogen (N2) pressure shown with a detecting pointer settling itself in the middle of the green zone on the scale. Device is considered unworkable, if the detecting pointer settles itself in the red zone on the scale (on zero section after discharge).
  3. Launch mechanism is launched by pushing upper handle down until full stop and keeping it in this position after launch. Please consider that the handle is blocked with a special safety ring to avoid accidental push when moving the device.
    Remember to pull the ring (PA2A-yellow cage) before pushing the handle!
  4. Rubber hose is designed for effective control of powder jet when extinguishing fire. When launching the device, please hold it firmly so that the reactive power of powder jet does not pull it from the hands. The device can be launched permanently and with intervals by pushing and releasing the upper handle. The remaining pressure in the shell after disengaging the device is preserved for not less than 5 minutes.
    The device must be discharged in a vertical position!

Safety rules

  1. As there is a permanent (15+1) bar pressure in the shell of the device, please follow safety rules when working with the device.
  2. Safekeeping of the device in the premises must be in the competence of the person in charge according to “Fire safety rules” No.440.
  3. Device must be inspected at least once per two years by delivering it for inspection to one of the specialised fire extinguishing equipment service centres. The same must be done every time after using it.
  4. In case devices are used in complicated climatic conditions, exposed to vibrations or petrol vapours, the running inspection time must be limited to one year.
  5. The shell of device must not have deformations, dints, corrosion, damaged paint or indicator, bent handles, please make sure the hose and the safety ring (PA2A – yellow cage) in the launch mechanism are not missing. Exploitation of device is not allowed without a manual in the state language attached to the shell!
    The detecting pointer must be in the green zone on the scale and the safety ring must be sealed!
  6. Device must be delivered to service centre for re-charge and inspection every time after it has been used.
    It is forbidden to use foam fire extinguishers for extinguishing fire on electric devices under voltage.

    Please follow the restrictions of exploitation temperature!

Guaranty

  1. “Valpro” Ltd. (manufacturer) guarantees compliance of technical parameters of device to the norms and standard operation for 24 months after date of production (charge) that is printed on the shell of the device and recorded in the certificate under condition that the above mentioned requirements of the usage of the device are executed.
  2. In case during the guarantee period the pressure in the shell of device has decreased (the detecting pointer settles itself in the red zone on the scale), the manufacturer undertakes to replace the device or perform a repair free of charge upon the user’s request under condition that the abovementioned requirements of the usage of device are executed.